
|
No Combustion Air |
|
If the unit is not burning the pellets at all or is not
burning them as completely as it should , check the following. |
|
1. Is the exhaust blower running? This blower is responsible for
both the exhaust and pulling combustion air through the fire. |
|
2. Is the installation done to manufacturers specs? These units
must have proper airflow through them in order to function properly,
deviation from the manufacturers instructions for installation
(including outside air intake) can cause problems with combustion
airflow. |
|
3. Has the stove/flue been cleaned? These units must be
cleaned out according the the schedule in the manual. This would also
include cleaning of the flue system. If the stove or the flue become
loaded with excess ash, the blockage from this ash will generally cause
poor performance from the unit. |
|
4. Are the stove's gaskets serviceable? Good gaskets are
essential to good performance, leaky gaskets can change airflow through
the stove causing burn related problems. |
|
5. Is the stove being run with the hopper lid open? England's
pellet units should NEVER be run
with the hopper lid open or unlatched. the stove could pull air through
the feed system. This not only will cause dirtier burning, it could
cause "smoke back" during power failure if the unit is running. |
|
|
|
If you have any further questions or concerns, please contact Customer Service at:
1-800-245-6489
|
|
|
|
Copyright © 2005
England's Stove Works, Inc. All rights reserved. Revised:
11/07/2008
|
|
This web site, including all pictures, description and
information of any sort contained therein is intended for the sole use of
customers and representatives of England's Stove Works, Inc. No part of
this web site or the information contained therein may be reproduced
without express written permission from England's Stove Works, Inc..
|
|