No Combustion Air
 

If the unit is not burning the pellets at all or is not burning them as completely as it should , check the following.
 

1. Is the exhaust blower running?  This blower is responsible for both the exhaust and pulling combustion air through the fire.
 

2. Is the installation done to manufacturers specs? These units must have proper airflow through them in order to function properly, deviation from the manufacturers instructions for installation (including outside air intake) can cause problems with combustion airflow.
 

3. Has the stove/flue been cleaned? These units must be cleaned out according the the schedule in the manual. This would also include cleaning of the flue system. If the stove or the flue become loaded with excess ash, the blockage from this ash will generally cause poor performance from the unit.
 

4. Are the stove's gaskets serviceable?  Good gaskets are essential to good performance, leaky gaskets can change airflow through the stove causing burn related problems.
 

5. Is the stove being run with the hopper lid open? England's pellet units should NEVER be run with the hopper lid open or unlatched. the stove could pull air through the feed system. This not only will cause dirtier burning, it could cause "smoke back" during power failure if the unit is running.

 

Click on the links below
for more information

 

Replacing Combustion Blower
Venting Page
Cleaning Page
Gasket Maintenance Page
 

If you have any further questions or concerns, please contact Customer Service at:
1-800-245-6489

Copyright © 2005   England's Stove Works, Inc.   All rights reserved.
Revised:  11/07/2008

This web site, including all pictures, description and information of any sort contained therein is intended for the sole use of customers and representatives of England's Stove Works, Inc. No part of this web site or the information contained therein may be reproduced without express written permission from England's Stove Works, Inc..